bagaimana boleh kami menolong anda
First, let's look at their definitions
Two-wire system: Two wires transmit power and transmit signals, that is, the load output by the sensor and the power supply are connected in series, and the power supply is introduced from the outside, and connected in series with the load to drive the load.
Three-wire system: The three-wire sensor is that the positive terminal of the power supply and the positive terminal of the signal output are separated, but they share a COM terminal.
Four-wire system: two wires for power and two wires for signal. Power and signal work separately.
The title of a few-wire system came into being only after the birth of the two-wire system transmitter. This is the result of the wide application of electronic amplifiers in instruments . The essence of amplification is an energy conversion process, which cannot be separated from power supply. Therefore, the four-wire transmitter appeared first; that is, two wires are responsible for the power supply, and the other two wires are responsible for outputting the converted and amplified signal (such as voltage , current , etc.). But at present, many transmitters use two-wire system. Next, let's take a look at the differences between different wire transmitters?
Differences between different wire transmitters
One, two-wire system
To realize a two-wire transmitter, the following conditions must be met at the same time:
1. V≤Emin-ImaxRLmax
The output voltage V of the transmitter is equal to the specified low power supply voltage minus the voltage drop of the current on the load resistance and transmission lead resistance.
2. I≤Imin
The normal working current I of the transmitter must be less than or equal to the output current of the transmitter.
3. P<Imin(Emin-IminRLmax)
The minimum power consumption P of the transmitter cannot exceed the above formula, usually <90mW.
In the formula: Emin=low power supply voltage, for most instruments Emin=24(1-5%)=22.8V, 5% is the allowable negative variation of 24V power supply;
Imax=20mA;
Imin=4mA;
RLmax=250Ω+transmission wire resistance.
If the pressure transmitter meets the above three conditions in design , two-wire transmission can be realized. The so-called two-wire system means that the power supply and the load are connected in series, and there is a common point, while the signal connection and power supply between the field transmitter and the control room wires , which are both power lines and signal lines. The two-wire transmitter provides a static working current for the transmitter because the starting point current of the signal is 4mA DC. At the same time, the electrical zero point of the instrument is 4mA DC, which does not coincide with the mechanical zero point. This "live zero point" is conducive to identifying power failure and Faults such as disconnection. Moreover, the two-wire system is also convenient to use a safety barrier, which is conducive to safety and explosion protection.
|
|
|
|